E6581741h
TOSVERT VF-MB1/S15
EtherNet/IP™ - Modbus
®
TCP option
Function Manual
IPE002Z
NOTICE
1. Read this manual before installing or operating. Keep this instruction manual on hand
of the end user, and make use of this manual in maintenance and inspection.
2. All information contained in this manual will be changed without notice. Please
contact your Toshiba distributor to confirm the latest information.
Vedere la pagina 0
1 2 3 4 5 6 ... 88 89

Sommario

Pagina 1 - E6581741h

E6581741h TOSVERT VF-MB1/S15 EtherNet/IP™ - Modbus® TCP option Function Manual IPE002Z NOTICE 1. Read th

Pagina 2 - Caution

E6581741 - 9 - Title Communication No. Function Description Factory settingc500 C500 Protocol (*3) This parameter is used to set the protocol of th

Pagina 3 - Table of Contents

E6581741 - 10 - EtherNet/IP parameters Title Communication No. Function Description Factory settingc536 C536 EtherNet Error Monitor of the EtherNet

Pagina 4

E6581741 - 11 - 3.2. The details of the parameter setting 3.2.1. Device name (c081-c096) This option module can set the "Device name" o

Pagina 5 - 2. Names and functions

E6581741 - 12 - 3.2.2. Assigning IP addresses (c504, c505-c516) The drive needs 3 (4-Modbus TCP) IP addresses. *The drive IP address. *The subnet m

Pagina 6

E6581741 - 13 - 3.2.3. Network error detection (c100 - c103, c523) ▼Display of trip information err8 (Optional unit fault 1: 1BH): Network error st

Pagina 7 - 2.4. LED indicator

E6581741 - 14 - 3.2.4. Command data (c001-c006), Monitor data (c021-c026) The outline is indicated about the setting item of parameter c001 – c006 a

Pagina 8 - 3. Parameters

E6581741 - 15 - 3.2.4.2. fa06 (Communication command1) bit Function 0 1 Note 0 Preset speed operation frequencies 1 1 Preset speed operation fr

Pagina 9

E6581741 - 16 - 3.2.4.3. fa23 (Communication command 2) bit Function 0 1 Note 0 (Reserved) - - - 1 Electric power quantity reset OFF Reset E

Pagina 10 - E6581741

E6581741 - 17 - 3.2.4.4. fa07 (frequency reference from internal option) Frequency reference is set up by 0.01Hz unit and the hexadecimal number.

Pagina 11 - Warning

E6581741 - 18 - 3.2.4.7. fd01 (Inverter operating status 1) bit Function 0 1 Note 0 Failure FL No output Under in progress - 1 Failure Not t

Pagina 12

E6581741 - 1 - - 1 -Introduction Thank you for purchasing the “EtherNet/IP™ - Modbus® TCP option (IPE002Z)” for TOSVERT VF-MB1/S15 inverter. Before

Pagina 13

E6581741 - 19 - 3.2.4.9. fd03 (Output current) The output current is read into 0.01% of units and by the hexadecimal number. For example, when t

Pagina 14

E6581741 - 20 - 3.2.4.13. fc91 (Alarm code) bit Function 0 1 Remarks (Code displayed on the panel) 0 Over-current alarm Normal Alarming c flickin

Pagina 15

E6581741 - 21 - 3.2.4.15. fd07 (Output TB Status) bit TB Name Function (Parameter) 0 1 0 RY-RC Output terminal function selection 1A (f130

Pagina 16

E6581741 - 22 - 4. Objects This section contains the object specifications for all EtherNet/IP objects currently supported by the “IPE002Z”. Table 1

Pagina 17

E6581741 - 23 - 4.1. Identity Object (0x01) Class code 0x01. This object provides identification of and general information about the device. C

Pagina 18

E6581741 - 24 - Attribute 5 State Descriptions Adapted from document [CIP] “THE CIP NETWORKS LIBRARY” Bit Called Definition 0 Owned TRUE indicat

Pagina 19

E6581741 - 25 - 4.2. Message Router Object (0x02) Class code 0x02. The Message Router Object provides a messaging connection point through which

Pagina 20

E6581741 - 26 - 4.3. Assembly Object (0x04) Class code 0x04. The Assembly Object binds attributes of multiple objects, which allows data to or fr

Pagina 21

E6581741 - 27 - 4.4. Connection Manager Object (0x06) Class code 0x06. Use this object for connection and connectionless communications, includ

Pagina 22

E6581741 - 28 - 4.5. Motor Data Object (0x28) Class code 0x28. This object serves as a database for motor parameters. Class Attributes Instance

Pagina 23 - 4. Objects

E6581741 - 2 - Table of Contents 1. OVERVIEW ...

Pagina 24 - 4.1. Identity Object (0x01)

E6581741 - 29 - 4.6. Control Supervisor Object (0x29) Class code 0x29. This object models all the management functions for devices within the “Hi

Pagina 25

E6581741 - 30 - Instance Services Service Code Service Name Description of Service 0x05 Reset Resets the drive to the start-up state. 0x0E G

Pagina 26

E6581741 - 31 - 4.6.1. Run/Stop Event Matrix Run1 Run2 Trigger Event Run Type 0 0 Stop No Action 0 -> 1 0 Run Run1 0 0 -> 1 Run Ru

Pagina 27 - 4.3. Assembly Object (0x04)

E6581741 - 32 - 4.7. AC/DC Drive Object (0x2A) Class code 0x2A. This object models the functions specific to an AC or DC Drive. e.g. speed ramp,

Pagina 28

E6581741 - 33 - 4.8. Parameter Objects (0x64) Class code 0x64. This object provides VF-MB1/ S15’s Parameter access. Range Address accessed: Input

Pagina 29

E6581741 - 34 - Instance Services Service Code Service Name Description of Service 0x0E Get_Attribute_Single Read one attribute 0x10 Set_Attribu

Pagina 30

E6581741 - 35 - 4.9. Parameter Objects (0x65) Class code 0x65. This object provides VF-MB1/S15’s Parameter access. Range Address accessed: Input In

Pagina 31

E6581741 - 36 - 4.10. Port Object (0xF4) Class code 0xF4. The Port Object enumerates the CIP ports present on the device. One instance exists for

Pagina 32 - 4.6.2. State of the drive

E6581741 - 37 - 4.11. TCP/IP interface Object (0xF5) Class code 0xF5. The TCP/IP Interface Object provides the mechanism to configure a device’s TCP

Pagina 33

E6581741 - 38 - Instance 1 Attribute Instance Attribute ID Access Name Data type Details 1 Get Status DWORD Bits 0 -3 : Interface configurat

Pagina 34

E6581741 - 3 - 8.7. "23 (0x17) Read/Write Multiple Registers" function...

Pagina 35

E6581741 - 39 - Instance Attribute ID Access Name Data type Details Mcast Config STRUCT of IP Multicast address configuration Alloc Config US

Pagina 36

E6581741 - 40 - 4.12. Ethernet link object (0xF6) Class code 0xF6: The Ethernet Link Object maintains link-specific counters and status information

Pagina 37 - 4.10. Port Object (0xF4)

E6581741 - 41 - Instance 1 Attribute Instance Attribute ID Access Name Data type Details 1 Get Interface Speed UDINT Interface speed currently

Pagina 38

E6581741 - 42 - Instance Attribute ID Access Name Data type Details Media Counters STRUCT of Media-specific counters Alignment Errors UDINT

Pagina 39

E6581741 - 43 - Instance 2 Attribute Instance Attribute ID Access Name Data type Details 1 Get Interface Speed UDINT Interface speed currently

Pagina 40

E6581741 - 44 - 5. Configuration of the assemblies 5.1. List of Assembly Object Instance Output Instance Instance name Number (Hex) Size CIP ba

Pagina 41

E6581741 - 45 - 5.1.1. Instance 20: CIP basic speed control output Instance 20 mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0

Pagina 42

E6581741 - 46 - 5.1.3. Instance 21: CIP extended speed control output Instance 21 mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Pagina 43

E6581741 - 47 - 5.1.5. Instance 100: Native drive output Instance 100 mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 DC brakin

Pagina 44

E6581741 - 48 - Examples of Instance 100/150 ① Stop Instance Byte 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Hex. 1, 0 0 0 00000000000 0 0 0 0x

Pagina 45 - Input Instance

E6581741 - 4 - 1. Overview The EtherNet/IP™ - Modbus® TCP option (IPE002Z) allows the VF-MB1/S15 inverter to be connected into the EtherNet/IP™ - Mo

Pagina 46

E6581741 - 49 - 5.1.7. Instance 101: Native drive output Instance 101 mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 - Net Ref

Pagina 47

E6581741 - 50 - Examples of Instance 101/151 Access the inverter parameter is enabled using byte 4 to 6 of this Instance. Set the communication nu

Pagina 48

E6581741 - 51 - 5.1.9. Instance 102: Native drive output Instance 102 mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 c001 Com

Pagina 49

E6581741 - 52 - 5.1.11. Instance 105: TOSHIBA specific output Instance 105 mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 1 F

Pagina 50

E6581741 - 53 - Examples of Instance 105/155 Access the inverter parameter is enabled using byte 1 to 5 of this Instance. Set the communication nu

Pagina 51

E6581741 - 54 - 6. About EDS file As for acquisition of an EDS file for VF-MB1 and VF-S15, please contact your Toshiba distributor. 7. Integratio

Pagina 52

E6581741 - 55 - 7.2. Add a EtherNet/IP scanner to the I/O configuration Right-click the I/O Configuration, and select “New Module”.

Pagina 53

E6581741 - 56 - Select the Module as below. Select revision of drive. Put in Name and IP address, and press “OK” button.

Pagina 54

E6581741 - 57 - 7.3. Configure the VF-MB1/S15 EtherNet/IP module Right-click the EtherNet/IP scanner, and select “New Module”.

Pagina 55 - 7. Integration in RSLogix™

E6581741 - 58 - Above the Allen-Bradley drive profile is selected. Select the format of the data. Above the CIP basic speed control

Pagina 56

E6581741 - 5 - 2.2. RJ45 connector pin layout The EtherNet/IP™ - Modbus® TCP option is equipped with two shielded RJ45 connectors. When you use VF

Pagina 57

E6581741 - 59 - 7.4. Download the program to the PLC The first download follows the following procedure. Select the using

Pagina 58

E6581741 - 60 - Select the "Download." Once again, select the "Download."

Pagina 59

E6581741 - 61 - 7.5. Edit the I/O scan data Open the "Controller Tags." Set to the "Offline" if change the

Pagina 60

E6581741 - 62 - Download the changed data to the PLC. : "Communications" J "Download" After the setting i

Pagina 61

E6581741 - 63 -

Pagina 62 - 7.5. Edit the I/O scan data

E6581741 - 64 - 8. Modbus TCP server 8.1. Modbus TCP frames Modbus TCP frames consist of a header and a Modbus request. Header format: Byte Descr

Pagina 63

E6581741 - 65 - 8.4. "03 (0x03) Read Holding Registers" function The Modbus request is used to read the values of a number (No. of Points

Pagina 64

E6581741 - 66 - 8.5. "06 (0x06) Write Single Register" function This Modbus request is used to write a given value (Present Data) to the

Pagina 65 - 8. Modbus TCP server

E6581741 - 67 - 8.6. "16 (0x10) Write Multiple Registers" function This Modbus request is used to write a number (No. of Registers) of ad

Pagina 66

E6581741 - 68 - 8.7. "23 (0x17) Read/Write Multiple Registers" function The "Read/Write Multiple Registers" service is reserved

Pagina 67

E6581741 - 6 - 2.4. LED indicator The LED shows the present status of the network and module. The behavior of LNK LED Link Activity Protocol

Pagina 68

E6581741 - 69 - 8.8. "43 (0x2B) Read Device identification" function The "Read/Write Multiple Registers" service is reserved fo

Pagina 69

E6581741 - 70 - Response format: (ID = 251) Byte Meaning With the IPE002Z 0 Function Code = 2Bh 2Bh 1 Type of MEI 0Eh 2 Read Device ID code

Pagina 70

E6581741 - 71 - 8.9. Parameter data It is explanation by the reference method of the list of parameters of the VF-MB1 or VF-S15 series as follows. F

Pagina 71

E6581741 - 72 - 9. IO Scanning service 9.1. Presentation The IO Scanning service is used to exchange I/O data between:  A controller or PLC (IO Sc

Pagina 72 - 8.9. Parameter data

E6581741 - 73 - 10. Example of the setup with PL7™ It is an example of the setup using PLC (PL7™) made by Schneider electric as follows. 10.1. Def

Pagina 73 - 9. IO Scanning service

E6581741 - 74 - 10.2. BOOTP configuration The BOOTP server function consists of allocating BOOTP clients their IP addresses. The activation conditio

Pagina 74

E6581741 - 75 - 10.3. Configuring Modbus messaging To use Modbus messaging in PL7, the “IP address”, “Subnet mask” and “Gateway address” parameters

Pagina 75 - 10.2. BOOTP configuration

E6581741 - 76 - 10.4. Configuring periodic variables This window is used to configure the IO Scanning function, described in the IO Scanning Service

Pagina 76

E6581741 - 77 - 11. Command & Setpoint selection (Local/Remote) Indication to display Local/Remote mode is on the inverter unit (Refer to the i

Pagina 77

E6581741 - 78 - <Example of setting> The example below shows how to configure the local/remote operation. F terminal ... Operatin

Pagina 78

E6581741 - 7 - 3. Parameters 3.1. Communication parameters Set up the inverter parameters as follows. It is necessary to reset the inverter to upd

Pagina 79 - EtherNet/IP-Modbus TCP

E6581741 - 79 - 12. Unusual diagnosis 12.1. Option error An error message is displayed when the hardware error or software error or lose of connect

Pagina 80 - 12. Unusual diagnosis

E6581741 - 80 - 13. WebServer The option has webserver function. Writing and reading the drive's parameter and the communication can be monito

Pagina 81 - 13. WebServer

E6581741 - 81 - From the TOSVERT home page, you can access to 3 main menus:  Monitoring  Network setup  Diagnostics 13.2. Web

Pagina 82 - 13.2. Web pages structure

E6581741 - 82 - 13.3. Drive monitor (Main menu: Monitoring) The state of the drive can be confirmed on this page.

Pagina 83

E6581741 - 83 - 13.4. Drive parameters (Main menu: Monitoring) The parameters of the drive can be set on this page. The left column is used to selec

Pagina 84

E6581741 - 84 - Input the write value to popup window.

Pagina 85

E6581741 - 85 - 13.5. Network parameters (Main menu: Network Setup) The network parameters of the drive can be confirmed on this page.

Pagina 86

E6581741 - 86 - 13.7. EthIP scanner (Main menu: Network Setup) The I/O scanner of the EtherNet/IP protocol can be set on this page.

Pagina 87

E6581741 - 87 - 13.8. Administration (Main menu: Network Setup) The "web read password" and "web write password" of the webserve

Pagina 88

E6581741 - 88 - 13.9. TCP/IP statistics (Main menu: Diagnostics) You can check TCP/IP status on this page. - 88E-

Pagina 89

E6581741 - 8 - Title Communication No. Function Description Factory settingc021 C021 Scanner output 1 address (*3)0: - 1: fd01 (Status informatio